EBS2L REC – RCCB

Sold By: : August Auto Agencies Ltd. Availability:

Compare
Sold By: : August Auto Agencies Ltd. Category:

Product Description

Function

The Tele REC relays automatically reclose the RCCB after on earth leakage or a manual disconnect. The relay will attempt to re-close 6 times with different time intervals between re-close attempts. After 6 unsuccessful attempts the Tele REC is locked.

 

Technical Parameter

Model name Tele REC Reconnecting
Standard IEC/EN 61008
Poles 2P, 4P
Product Function Leakage protection, isolation function
Rated voltage Un(V) 230/400V AC 50/60Hz
Rated current (A) ≤25, ≤40, ≤63
Connection type Tunnel style, Pin style, U style
Action style AC, A
Installation style Standard 35mm guide
Im I△m (A) 500
Inc I△n (A) 6,000
Mechanical life (times) 10,000
Protection degree IP20